01 | Air exchange, CO₂ and heat
Air change and units
n [h⁻¹] · V [m³] net room volume · V̇ [m³/h]. 1 m³/s = 3600 m³/h; 1 L/h = 0.001 m³/h; 1 ppm = 10⁻⁶ m³/m³.
CO₂ balance – steady state
Ṁ [m³/h] = occupants × CO₂ generation per person. cᵢ, cₑ [m³/m³] indoor/outdoor. Convert ppm by × 10⁻⁶. Fully mixed air.
CO₂ rise without ventilation
t [h], concentrations as volume fractions; t × 60 for minutes. Constant source, no infiltration.
Decay measurement
t [h] = minutes / 60. c₀, c(t), cₑ may all be in ppm. No CO₂ generation during measurement.
Ventilation heat loss and energy
Q̇ [W], V̇ [m³/h], Δθ = θᵢ − θₑ [K], t [h], E [kWh]. Heating oil: E / 10 [L] (10 kWh/L, ignoring efficiency). General: Q̇ = ρcₚV̇Δθ with V̇ in m³/s.
Reference values | Value |
|---|---|
Outdoor CO₂ | 420 ppm |
Pettenkofer / unacceptable | 1000 / > 2000 ppm |
CO₂ per seated person | 18–20 l/h |
Outdoor air per person | 25–35 m³/h |
02 | Airtightness and openings
Blower-door test
V̇₅₀ [m³/h] at 50 Pa; n₅₀ [h⁻¹]. Infiltration is a rule of thumb only. Older unrenovated buildings > 4; new buildings approx. 1–2; passive house ≤ 0.6 h⁻¹ (indicative).
Bernoulli and large opening
Δp [Pa], ρ [kg/m³], v [m/s], A [m²] geometric, C_d ≈ 0.6; V̇ [m³/s]. Effective flow area = C_d A: apply C_d only once.
Cracks – power law
V̇ [m³/h]; C [m³/(h·Paᵝ)], a [m³/(h·m·Pa²⁄³)], l [m]. β = 0.5 turbulent; ≈ 0.65 cracks; 1 laminar. β is the flow exponent (n in the lecture), not the air change rate.
Parallel – same pressure difference
Same C_d. Openings side by side; add flow rates.
Series – same flow rate
Same C_d; Δp = ΣΔpᵢ. Aeff is the equivalent geometric area. Smallest opening limits flow; calculate V̇ using C_d Aeff. If A₁ = A₂ = A: Aeff = A/√2.
03 | Wind pressure and cross-ventilation
Wind profile
v [m/s]; z, zref [m]; zref usually 10 m; α terrain exponent. First find v at building height.
Dynamic and façade pressure
q, pw [Pa]; ρ ≈ 1.2 kg/m³; v [m/s]; cₚ dimensionless. Windward (+), leeward (−). Double speed → four times pressure.
Wind-driven cross-ventilation
Same wind speed at both openings, same C_d. Aeff from series formula, V̇ [m³/s]; × 3600 / V for n [h⁻¹]. Sign of Δp determines direction. One opening only: no steady cross-flow in this model.
Terrain | α | Façade | cₚ |
|---|---|---|---|
Open / lake | 0.10–0.15 | Windward | +0.5…+0.8 |
Suburb / forest | 0.20–0.25 | Leeward | −0.3…−0.5 |
City centre | 0.30–0.40 | Side wall | −0.5…−0.7 |
Flat roof | −0.5…−1.0 | ||
Edges / corners | ≈ −1.5 |
04 | Thermal buoyancy
Air density and temperature
T [K], θ [°C], ρ [kg/m³] at p ≈ 101325 Pa. g = 9.81 m/s²; ΔT = |Tᵢ − Tₑ| [K].
Stack effect – pressure difference
h [m] vertical separation; Δp [Pa]. In winter: negative indoor pressure below, positive above (without wind).
Single-sided window
A [m²] total window area; H [m] window height; V̇ [m³/s] supply or exhaust, not their sum. At fixed area: V̇ ∝ √H. Room depth ≲ 2.5 × room height (rule of thumb).
Stack ventilation – two openings
Aeff equivalent geometric series area, h [m] vertical opening separation, V̇ [m³/s]. Alternatively use Bernoulli with |Δp| and representative ρ.
Neutral pressure plane
A₁ lower, A₂ upper; zN measured from lower opening [m]. Same C_d, two openings, no wind, density difference neglected in flow formula. Plane closer to larger opening.
Wind and buoyancy
First approximation for reinforcing effects only. For opposing effects, balance signed pressures rather than adding flow rates. Single-zone model: solve pᵢ iteratively.
Exam workflow: temperatures → density/pressure → equivalent area → flow rate → ×3600 → air change rate. For wind: start with wind profile.
Source: HSLU, 11_Luftaustausch_oL.pdf, pp. 8–40. CO₂ rise, energy conversion and neutral plane: derived relations for exercises 1, 2 and 6.