11 – Air Exchange | Exam Formula Sheet

01 | Air exchange, CO₂ and heat

Air change and units

n=V˙VV˙=nVV=L B H\boxed{n=\frac{\dot V}{V}}\quad \dot V=nV\qquad V=L\,B\,H

n [h⁻¹] · V [m³] net room volume · V̇ [m³/h]. 1 m³/s = 3600 m³/h; 1 L/h = 0.001 m³/h; 1 ppm = 10⁻⁶ m³/m³.

CO₂ balance – steady state

V˙=M˙CO2ci−ceci=ce+M˙CO2V˙\boxed{\dot V=\frac{\dot M_{CO_2}}{c_i-c_e}}\qquad c_i=c_e+\frac{\dot M_{CO_2}}{\dot V}

Ṁ [m³/h] = occupants × CO₂ generation per person. cᵢ, cₑ [m³/m³] indoor/outdoor. Convert ppm by × 10⁻⁶. Fully mixed air.

CO₂ rise without ventilation

t=V(c−c0)M˙CO2c(t)=c0+M˙CO2Vt\boxed{t=\frac{V(c-c_0)}{\dot M_{CO_2}}}\qquad c(t)=c_0+\frac{\dot M_{CO_2}}{V}t

t [h], concentrations as volume fractions; t × 60 for minutes. Constant source, no infiltration.

Decay measurement

n=1tln⁡ ⁣(c0−cec(t)−ce)c(t)=ce+(c0−ce)e−nt\boxed{n=\frac{1}{t}\ln\!\left(\frac{c_0-c_e}{c(t)-c_e}\right)}\qquad c(t)=c_e+(c_0-c_e)e^{-nt}

t [h] = minutes / 60. c₀, c(t), cₑ may all be in ppm. No CO₂ generation during measurement.

Ventilation heat loss and energy

Q˙v=0.34 V˙ Δθ=0.34 nV ΔθE=Q˙vt1000\boxed{\dot Q_v=0.34\,\dot V\,\Delta\theta=0.34\,nV\,\Delta\theta}\qquad E=\frac{\dot Q_v t}{1000}

Q̇ [W], V̇ [m³/h], Δθ = θᵢ − θₑ [K], t [h], E [kWh]. Heating oil: E / 10 [L] (10 kWh/L, ignoring efficiency). General: Q̇ = ρcₚV̇Δθ with V̇ in m³/s.

Reference values

Value

Outdoor CO₂

420 ppm

Pettenkofer / unacceptable

1000 / > 2000 ppm

CO₂ per seated person

18–20 l/h

Outdoor air per person

25–35 m³/h

02 | Airtightness and openings

Blower-door test

n50=V˙50Vninf≈n5020\boxed{n_{50}=\frac{\dot V_{50}}{V}}\qquad n_{\mathrm{inf}}\approx\frac{n_{50}}{20}

V̇₅₀ [m³/h] at 50 Pa; n₅₀ [h⁻¹]. Infiltration is a rule of thumb only. Older unrenovated buildings > 4; new buildings approx. 1–2; passive house ≤ 0.6 h⁻¹ (indicative).

Bernoulli and large opening

v=2∣Δp∣ρV˙=CdA2∣Δp∣ρ\boxed{v=\sqrt{\frac{2|\Delta p|}{\rho}}}\qquad \boxed{\dot V=C_d A\sqrt{\frac{2|\Delta p|}{\rho}}}

Δp [Pa], ρ [kg/m³], v [m/s], A [m²] geometric, C_d ≈ 0.6; V̇ [m³/s]. Effective flow area = C_d A: apply C_d only once.

Cracks – power law

V˙=C∣Δp∣βV˙=a l ∣Δp∣2/3\boxed{\dot V=C|\Delta p|^{\beta}}\qquad \boxed{\dot V=a\,l\,|\Delta p|^{2/3}}

V̇ [m³/h]; C [m³/(h·Paᵝ)], a [m³/(h·m·Pa²⁄³)], l [m]. β = 0.5 turbulent; ≈ 0.65 cracks; 1 laminar. β is the flow exponent (n in the lecture), not the air change rate.

Parallel – same pressure difference

Aeff=∑iAiV˙=∑iV˙i\boxed{A_{\mathrm{eff}}=\sum_i A_i}\qquad \dot V=\sum_i\dot V_i

Same C_d. Openings side by side; add flow rates.

Series – same flow rate

1Aeff2=∑i1Ai2Aeff=A1A2A12+A22\boxed{\frac{1}{A_{\mathrm{eff}}^2}=\sum_i\frac{1}{A_i^2}}\qquad \boxed{A_{\mathrm{eff}}=\frac{A_1 A_2}{\sqrt{A_1^2+A_2^2}}}

Same C_d; Δp = ΣΔpᵢ. Aeff is the equivalent geometric area. Smallest opening limits flow; calculate V̇ using C_d Aeff. If A₁ = A₂ = A: Aeff = A/√2.

03 | Wind pressure and cross-ventilation

Wind profile

v(z)=vref(zzref)α\boxed{v(z)=v_{\mathrm{ref}}\left(\frac{z}{z_{\mathrm{ref}}}\right)^\alpha}

v [m/s]; z, zref [m]; zref usually 10 m; α terrain exponent. First find v at building height.

Dynamic and façade pressure

q=ρ2v2≈0.6v2pw=cpq\boxed{q=\frac{\rho}{2}v^2\approx0.6v^2}\qquad \boxed{p_w=c_pq}

q, pw [Pa]; ρ ≈ 1.2 kg/m³; v [m/s]; cₚ dimensionless. Windward (+), leeward (−). Double speed → four times pressure.

Wind-driven cross-ventilation

Δp=(cp,1−cp,2)qV˙=CdAeffv∣cp,1−cp,2∣\boxed{\Delta p=(c_{p,1}-c_{p,2})q}\qquad \boxed{\dot V=C_d A_{\mathrm{eff}}v\sqrt{|c_{p,1}-c_{p,2}|}}

Same wind speed at both openings, same C_d. Aeff from series formula, V̇ [m³/s]; × 3600 / V for n [h⁻¹]. Sign of Δp determines direction. One opening only: no steady cross-flow in this model.

Terrain

α

Façade

cₚ

Open / lake

0.10–0.15

Windward

+0.5…+0.8

Suburb / forest

0.20–0.25

Leeward

−0.3…−0.5

City centre

0.30–0.40

Side wall

−0.5…−0.7

Flat roof

−0.5…−1.0

Edges / corners

≈ −1.5

04 | Thermal buoyancy

Air density and temperature

T=θ+273.15ρ≈353TT‾=Ti+Te2\boxed{T=\theta+273.15}\qquad \boxed{\rho\approx\frac{353}{T}}\qquad \overline T=\frac{T_i+T_e}{2}

T [K], θ [°C], ρ [kg/m³] at p ≈ 101325 Pa. g = 9.81 m/s²; ΔT = |Tᵢ − Tₑ| [K].

Stack effect – pressure difference

Δp=gh(ρe−ρi)≈0.04h(θi−θe)\boxed{\Delta p=gh(\rho_e-\rho_i)\approx0.04h(\theta_i-\theta_e)}

h [m] vertical separation; Δp [Pa]. In winter: negative indoor pressure below, positive above (without wind).

Single-sided window

V˙=Cd3AgHΔTT‾\boxed{\dot V=\frac{C_d}{3}A\sqrt{gH\frac{\Delta T}{\overline T}}}

A [m²] total window area; H [m] window height; V̇ [m³/s] supply or exhaust, not their sum. At fixed area: V̇ ∝ √H. Room depth ≲ 2.5 × room height (rule of thumb).

Stack ventilation – two openings

V˙=CdAeff2ghΔTT‾\boxed{\dot V=C_d A_{\mathrm{eff}}\sqrt{2gh\frac{\Delta T}{\overline T}}}

Aeff equivalent geometric series area, h [m] vertical opening separation, V̇ [m³/s]. Alternatively use Bernoulli with |Δp| and representative ρ.

Neutral pressure plane

zN=hA22A12+A22Δpi∝1Ai2\boxed{z_N=h\frac{A_2^2}{A_1^2+A_2^2}}\qquad \Delta p_i\propto\frac{1}{A_i^2}

A₁ lower, A₂ upper; zN measured from lower opening [m]. Same C_d, two openings, no wind, density difference neglected in flow formula. Plane closer to larger opening.

Wind and buoyancy

V˙≈V˙W2+V˙Th2Δpj=pw,j+pth,j−pi∑jV˙j=0\dot V\approx\sqrt{\dot V_W^2+\dot V_{Th}^2}\qquad \Delta p_j=p_{w,j}+p_{th,j}-p_i\qquad \sum_j\dot V_j=0

First approximation for reinforcing effects only. For opposing effects, balance signed pressures rather than adding flow rates. Single-zone model: solve pᵢ iteratively.

Exam workflow: temperatures → density/pressure → equivalent area → flow rate → ×3600 → air change rate. For wind: start with wind profile.

Source: HSLU, 11_Luftaustausch_oL.pdf, pp. 8–40. CO₂ rise, energy conversion and neutral plane: derived relations for exercises 1, 2 and 6.